Pressed Steel Sectional Water Tank

General Specifications

Standard :

Pressed steel sectional water tank constructed with hydraulically pressed flanged panels, conform to BS 1564 : 1975 and SS 22 : 1979.

Materials :

The steel used in the manufacture of the tank plates, stays and cleats conform to the requirements of BS 4360 : 1972 grade 43A or ISO equivalent

Flanges of Plates :

Tank panels pressed with a combined double flange at an angle of 45 degree and 90 degree to the face of the plate in four sides

Stays and Cleats :

The stays and cleats are made of steel angle bar and steel plate

Bolts, Nuts and Washers :

Hot Dipped Galvanised steel bolts, nuts and washers for internal and external

Jointing Materials :

Non-toxic PVC foam to be used for all jointing between tank panel flanges

Nozzles for Connection :
Short pipe with flange or socket for all pipe connections
Ladder :
Aluminium or HDG Steel ladder for internal and external access, 300mm width
Tank Cover :
Panel type tank cover supported by trusses 530mm x 530mm square manhole and PVC air-vent supplied as standard for each compartment
Water Level Indicator :
Reverse Reading Pointer Mechanical Type (Cat & Mouse)
Finish :
Hot Dip Galvanished conform to ISO 1461

Standard Thickness for 1.22 m x 1.22 m Tank Panel

TYPE1.22 M (H)2.44 M (H)3.66 M (H)4.88 M (H)
Tank covers1.5 mm1.5 mm 1.5 mm1.5 mm
4th side panels   5.0 mm
3rd side panels  5.0 mm5.0 mm
2nd side panels 5.0 mm5.0 mm5.0 mm
1st side panels5.0 mm5.0 mm5.0 mm6.0 mm
Bottom panels5.0 mm5.0 mm5.0 mm6.0 mm

Standard Thickness for 1.0 m x 1.0 m Tank Panel

TYPE1.0M (H)2.0M (H)3.0M (H)4.0M (H)5.0M (H)
5th side panels    5.0 mm
4th side panels   5.0 mm5.0 mm
3rd side panels  5.0 mm5.0 mm5.0 mm
2nd side panels 5.0 mm5.0 mm5.0 mm5.0 mm
1st side panels5.0 mm5.0 mm5.0 mm5.0 mm5.0 mm
Bottom panels5.0 mm5.0 mm5.0 mm5.0 mm5.0 mm